Document Audience: | INTERNAL |
Document ID: | A0096-1 |
Title: | Enterprise 56" Rack non-compliance with safety standard UL1950/EN60950 |
Copyright Notice: | Copyright © 2005 Sun Microsystems, Inc. All Rights Reserved |
Update Date: | Fri Mar 07 00:00:00 MST 1997 |
---------------------------------------------------------------------
- Sun Proprietary/Confidential: Internal Use Only -
---------------------------------------------------------------------
FIELD CHANGE ORDER
(For Authorized Distribution by SunService)
FCO #: A0096-1
Status: inactive
Synopsis: Enterprise 56" Rack non-compliance with safety standard UL1950/EN60950Date: Mar/07/97
Keywords:
Enterprise 56" Rack non-compliance with safety standard UL1950/EN60950
Product Category: Systems / Power
Product Affected:
Enterprise 5000
Enterprise 6000
Enterprise 10000
Enterprise Cluster 5000-HA
Enterprise Cluster 6000-HA
Enterprise Cluster 5000-PDB
Enterprise Cluster 6000-PDB
SPARCstorage Array Model 214 RSM X796A
SPARCstorage Array Model 214 RSM X797A
SPARCstorage Array Model 219 RSM X6595A
SPARCstorage Array Model 219 RSM X6596A
Enterprise Expansion Cabinet X956A
Power Sequencer for Enterprise
Expansion Cabinet, RSM Array X6513A
SPARCstorage Array Model RSM2000 X6530A
SPARCstorage Array Model RSM2000 X6531A
SPARCstorage Array Model RSM 2000 15x 9.1gb 7200rpm X6534A
SPARCstorage Array Model RSM 2000 35x 9.1gb 7200rpm X6535A
Power Cord for Enterprise System and Mass Storage/Expansion Cabinet:
- Option 3800A - U.S. Version (NEMA L6-30P plug)
- Option 3848A - European Version (IEC-309 plug 32A 250VAC
Parts Affected:
530-2265-01 208/240 VAC 30A, power cord, U.S. Version
(NEMA L6-30P plug)
530-2266-01 208/240 VAC 30A, power cord, European Version
(IEC-309 plug 32A 250VAC)
300-1290-02 208/240 VAC 30A, Single Phase, Universal AC Sequencer
(Sherwood Enterprise Model 10)
F300-1290-02 208/240 VAC 30A, Single Phase, Universal AC Sequencer
(Sherwood Enterprise Model 10)
References:
Escalation number: CTE#508271 SO#5590725
ECO wo_10322
Stop Ship WW/001#03410
ECO wo_10344
WW/001#03407
802-3845-10 Ultra Enterprise 6000/5000/4000 Systems Manual
Issue Description:
The AC input box "Sequencer" and power cord have metal castings which
are unearthed and may not be adequately insulated from AC wiring
pursuant to UL1950/EN60950 international safety standard. International safety
standards, such as EN60950, allow for unearthed metal as long as primary
circuits and unearthed metal are separated by supplemental insulation.
Sequencer p/n 300-1290-02 and power cord p/n's 530-2266-01 and 530-2265-01
used on rack systems do not contain the supplemental insulation and so do
not meet this requirement.
Sun Operations has implemented Engineering Change Orders to rework both
the Power cables and Sequencer parts on all shipments effective Feb 20, 1997.
These engineering changes have received Agency UL approvals and with the
replacement of the power cable and sequencer at customer sites, the product
will be restored to compliance with the International safety standard
EN 60950 and UL1950.
Implementation:
---
| x | MANDATORY (Fully Pro-Active)
---
---
| | CONTROLLED PRO-ACTIVE (per Sun Geo Plan)
---
---
| | UPON FAILURE
---
Replacement Time Estimate:
30 minutes
Special Considerations:
While disconnecting the power cord, be sure to remove
the plug at the wall end of the power cord before
removing the plug at the other end.
Corrective Action:
1) Switch off the power to system and/or Expansion cabinets.
2) FIRST Disconnect the plug- the wall end -of the power cord,
THEN disconnect the plug at the sequencer end.
3) Replace the power cable as applicable:
530-2265-01 with 530-2265-02 OR
530-2266-01 with 530-2266-02.
4) Replace the power sequencer 300-1290-02 with 300-1290-03.
5) Return ANY replaced parts to the Sun supply location immediately,
making sure to reference FCO A0096-1 on the Defect Materials Tag.
NOTE THAT THE POWER CABLE IS NOT A CONSUMABLE AND BOTH REPLACED
PARTS MUST BE RETURNED.
Comments:
1) Reference the Ultra Enterprise 6000/5000/4000 Systems Manual,
802-3845-10 or greater, refer to section-Part 5, Appendix E,
page E-6 for step-by-step instructions. This Manual section is
also located on edist, see directions below for access.
================================================================================
Billing Type:
Sun will provide parts and On-Site Labor at no charge to all customers
regardless of contract or warranty status.
--------------------------------------------------------------------------
Implementation Footnote:
________________________
i) In case of Mandatory FCOs, SunService will attempt to contact all known
customers to recommend the part upgrade.
ii) For controlled proactive swap FCOs, SunService mission critical support
teams will initiate proactive swap efforts for their respective accounts,
as required.
iii) For Replace upon Failure FCOs, SunService partners will implement the
necessary corrective actions as and when they are required.
SunWeb Access:
______________
All released FINs and FCOs can be accessed internally on the SunWeb using your
favorite network browser as follows:
* Access the top level URL of http://cte.corp/FIN_FCO/
* From there, select the appropriate link to query or browse the FIN and
FCO Homepage collections.
Supporting documents for FIN/FCOs can be found on Edist. Edist can be
accessed internally at the following URL: http://edist.corp/.
* From there, follow the hyperlink path of "SunService Documentation" and
click on "FIN & FCO attachments", then choose the apropriate folder, FIN or
FCO. This will display supporting directories/files for FINs or FCOs.
--------------------------------------------------------------------------
General:
________
Send questions or comments to finfco-manager@cte.Corp
---------------------------------------------------------------------------