FIELD CHANGE ORDER
(For Authorized Distribution by SunService)
FCO #: A0165-1
Status: inactive
Synopsis: Any Battery Backup Unit over two years old may not have enough energy to hold data in the RSM2000 or A3000 controller's Write-Back Cache for 72 hours in the event of a power outage.Date: Jun/19/00
Keywords:
Any Battery Backup Unit over two years old may not have enough energy to hold data in the RSM2000 or A3000 controller's Write-Back Cache for 72 hours in the event of a power outage
Top FIN/FCO Report: Yes
Products Reference: RSM2000 / A3000 Battery Backup Unit (BBU)
Product Category: Storage / RSM ; Storage / A3000
Product Affected:
Mkt_ID Platform Model Description Serial Number
------ -------- ----- ----------- -------------
Systems Affected
------- --------
ANYSYS - - System Platform Independent -
X-options Affected
--------- --------
X6530A RSM 2000 - RSM2000 15*4.2Gb/5400 FWSCSI -
X6531A RSM 2000 - RSM2000 35*4.2Gb/5400 FWSCSI -
X6532A A3000 - StorEdge A3000 15*4.2Gb/7200 FWSCSI -
X6533A A3000 - StorEdge A3000 35*4.2Gb/7200 FWSCSI -
X6534A A3000 - StorEdge A3000 15*9.1Gb/7200 FWSCSI -
X6535A A3000 - StorEdge A3000 35*4.2Gb/7200 FWSCSI -
X6536A - - RSM2000/A3000 Controller -
Parts Affected:
Part Number Description Model
----------- ----------- -----
370-2434-01 Battery Canister-Sonoma -
(SCSI Devices)
Type Vendor Model SerialNumber(Min) SerialNumber(Max) Firmware
---- ------ ------- ------------------ ------------------ --------
N/A
References:
ECO: WO_13238
LEAP: 1073
MANUAL: 805-2781-10 RAID Manager 6.1 User's Guide
MANUAL: 805-2782-11 Sun RSM Array 2000 System Manual
MANUAL: 805-4057-10 Sun StorEdge RAID Manager 6.1.1 User's Guide
MANUAL: 805-4980-10 Sun StorEdge A3000 Controller Module Guide
MANUAL: 805-6887-10 Sun StorEdge RAID Manager 6.2 User's Guide
Issue Description:
The batteries in the Battery Backup Unit (BBU) of the RSM Array 2000 and the
StorEdge A3000 have a design life of two years. In order to ensure the BBU
can maintain the controller's Write-Back Cache (WBC) for the specified minimum
72 hour period during a power outage, the BBU must be replaced before the
batteries in the BBU exceed the two year designed life span.
The Battery Canister or BBU (Sun p/n 370-2434-01) provides no indication of
a battery which has a low charge or may have a hardware problem.
Corrective action was implemented in Sun Manufacturing via ECO# WO_13238 on
June 19, 1998 by releasing the 370-2434-02 which contains (Amber) fault and
(Green) charge indicator LEDs. The Amber LED indicates a hardware fault
within the BBU and the Green LED indicates a fully charged battery.
Corrective action was implemented in Enterprise Services via LEAP_1073 on
December 14th, 1999 which instructed the field to purge and scrap the
370-2434-01, and to set MAL to 370-2434-02.
Implementation:
---
| | MANDATORY (Fully Pro-Active)
---
---
| X | CONTROLLED PRO-ACTIVE (per Sun Geo Plan)
---
---
| | UPON FAILURE
---
Replacement Time Estimate:
30 minutes
Special Considerations:
The Storage A3500 is not affected as it began shipping with the 370-2434-02
in July of 1998. All Battery Backup Units (BBUs), regardless of dash level,
should be replaced every two years.
Corrective Action:
All customer storage Battery Backup Units (BBU) should be audited to verify
the installation or expiration label for the time remaining on them.
Once the battery life has been identified, customers should be advised of the
current status of these consumable items so replacement units can be ordered
and installed before the 2 year expiration date. Upon completion of an audit,
if any BBUs are nearing expiration, it is recommended they be replaced as
soon as is practicable.
Replace all 370-2434-01 on or before the end of 2 year design life has
expired with 370-2434-02.
Comments:
All Battery Backup Units (BBUs), regardless of dash level, should be
replaced every two years.
Billing Type:
Warranty: Sun will provide parts at no charge under Warranty
Service. On-Site Labor Rates are based on how the
system was initially installed.
Contract: Sun will provide parts at no charge. On-Site Labor Rates
are based on the type of service contract.
Non Contract: Sun will provide parts at no charge. Installation by
Sun is available based on the On-Site Labor Rates
defined in the Price List.
--------------------------------------------------------------------------
Implementation Footnote:
________________________
i) In case of Mandatory FCOs, Enterprise Services will attempt to contact
all known customers to recommend the part upgrade.
ii) For controlled proactive swap FCOs, Enterprise Services mission critical
support teams will initiate proactive swap efforts for their respective
accounts, as required.
iii) For Replace upon Failure FCOs, Enterprise Services partners will
implement the necessary corrective actions as and when they are
required.
--------------------------------------------------------------------------
All released FINs and FCOs can be accessed using your favorite network
browser as follows:
SunWeb Access:
______________
* Access the top level URL of http://sdpsweb.EBay/FIN_FCO/
* From there, select the appropriate link to query or browse the FIN and
FCO Homepage collections.
SunSolve Online Access:
_______________________
* Access the SunSolve Online URL at http://sunsolve.Central/
* From there, select the appropriate link to browse the FIN or FCO index.
Supporting Documents:
____________________
Supporting documents for FIN/FCOs can be found on Edist. Edist can be
accessed internally at the following URL: http://edist.Central/.
* From there, follow the hyperlink path of "SunService Documentation" and
click on "FIN & FCO attachments", then choose the appropriate folder,
FIN or FCO. This will display supporting directories/files for FINs or
FCOs.
Internet Access:
_______________
* Access the top level URL of https://infoserver.Sun.COM
--------------------------------------------------------------------------
General:
________
Send questions or comments to finfco-manager@Sun.COM
---------------------------------------------------------------------------