Document Audience:INTERNAL
Document ID:I0711-1
Title:The problem with Incorrectly mounted brackets on the switch
Copyright Notice:Copyright © 2005 Sun Microsystems, Inc. All Rights Reserved
Update Date:2001-10-10

---------------------------------------------------------------------
- Sun Proprietary/Confidential: Internal Use Only -
---------------------------------------------------------------------  
                            FIELD INFORMATION NOTICE
                  (For Authorized Distribution by SunService)
FIN #: I0711-1
Synopsis: The problem with Incorrectly mounted brackets on the switch
Create Date: Oct/10/01
Keywords: 

The problem with Incorrectly mounted brackets on the switch

SunAlert: No
Top FIN/FCO Report: No
Products Reference: 16 Port Fibre Channel Switch
Product Category: Storage / Service
Product Affected: 
Systems Affected
---------------- 
Mkt_ID        Platform   Model   Description                Serial Number
------        --------   -----   -----------                -------------
  -           ANYSYS       -     System Platform Independent      -


X-Options Affected
------------------
Mkt_ID        Platform   Model   Description                Serial Number
------        --------   -----   -----------                -------------
S6-XSW16-32P     -         -     16-Port Switch Python            -
Parts Affected: 
Part Number        Description                Model
-----------        -----------                -----
F370-4276-01       16-PORT SWITCH PYTHON        -
References: 
MANUAL: 806-6922-10: Sun StorEdge network FC switch-8 and switch-16 
                     Installation and Configuration Guide.

URL: http://sdpsweb.ebay/FIN_FCO/FIN/FINI0711-1_dir/rearbrkt.htm
     http://sdpsweb.ebay/FIN_FCO/FIN/FINI0711-1_dir/frontbrkt.htm
Issue Description: 
Some StorEdge Network FC Switch-16 units were assembled and shipped
from the vendor with their mounting brackets reversed.  This could
potentially result in these switches being installed backwards in the
72-inch StorEdge Expansion Cabinet.  This improper installation may
cause the inlet temperature of the switch to exceed its recommended
range and this could affect the performance and the life of the
switch.  In addition, the connecting fibre cables might be damaged by
hitting the rear cabinet door and may require replacement.
  
There are 4 mounting brackets for each switch, with 2 in the front and
2 in the back of the switch.  Please note the following descriptions of
the front-end and rear-end brackets and the mounting procedures for the
switch:

  Front-end bracket:
  ------------------

  . The front-end brackets are L-shaped.  
  . They should be mounted on the side of the switch closest to the air 
    intake perforation pattern.  
  . Both brackets should be mounted with the large chamfer (bevel) at the 
    top.
  . The mounting holes are countersunk for flat head screws.

  Rear-end brackets:
  ------------------  

  . The rear-end brackets are flat, rectangular-shaped, and have small
    chamfers on all 4 corners.
  . They should be mounted on the side of the switch closest to the GBIC's.  
  . The mounting hole are countersunk for flat head screws.  

  Note: Please refer to the photo's referenced in the Corrective Action 
        showing the proper bracket orientation for both front-end and 
        rear-end.

The following drawing shows the brackets installed incorrectly 
(first drawing) and correctly (second drawing) on the switch. 

     _                     _              |                   |
      | _________________ |               | _________________ |
      ||      Back       ||               ||      Back       ||
       |                 |                 |                 |
       |                 |                 |                 |
       |                 |                 |                 |
       |      SWITCH     |                 |      SWITCH     |
       |                 |                 |                 |
       |                 |                 |                 |
       |      Front      |                 |      Front      |
      ||_________________||               ||_________________||         
      |                   |              _|                   |_ 
      |                   |                                  

      INCORRECTLY INSTALLED                CORRECTLY INSTALLED
      

The instructions given in the "Sun StorEdge Network FC Switch-8 and
Switch-16 Installation and Configuration Guide", P/N 806-6922-10, are
correct if the brackets are mounted correctly on the switch.  Since the
pre-installed brackets on the switch may not be properly mounted, the
Field should use the above drawings as a reference to remove the
brackets from the switch and install them correctly before following
the instructions in the manual.  The guideline in the manual states
"From the front of the cabinet, slide the first switch into the lowest
of the mounting rails.  The GBIC side goes toward the back of the
rack." Incorrectly mounted brackets will hit the cabinet's front
mounting rails and not allow the switch to enter the cabinet.
    
This problem has occurred because the vendor's (Qlogic) assembly
instructions for the switch were incorrect.  The vendor has been
notified of the problem and digital photo's have been sent showing the
correct assembly.  An ECO will be processed to add a drawing to the
product specification, showing the correct orientation of the mounting
brackets.
Implementation: 
---
        |   |   MANDATORY (Fully Pro-Active)
         ---    
         
  
         ---
        |   |   CONTROLLED PRO-ACTIVE (per Sun Geo Plan) 
         --- 
         
                                
         ---
        | X |   REACTIVE (As Required)
         ---
Corrective Action: 
The following recommendation is provided as a guideline for authorized
Enterprise Services Field Representatives who may encounter the above 
mentioned problem.

Please adhere to the following guidelines to fix the problem:

  1. If the mounting brackets for the StorEdge Network FC Switch-16 are
     found to be incorrectly mounted, follow the instructions below and
     the photos shown at the following URLs.

        http://sdpsweb.ebay/FIN_FCO/FIN/FINI0711-1_dir/frontbrkt.htm 
        http://sdpsweb.ebay/FIN_FCO/FIN/FINI0711-1_dir/rearbrkt.htm  

  2. Disassemble the brackets by removing the screws, two per bracket.  

  3. Mount the two flat brackets closest to the GBIC end of the switch.
        The countersunk holes on the brackets must face outwards.  

  4. The L-shaped brackets are to be mounted closest to the fan end
	of the switch.  Orient the L-shaped bracket so that the flange
	with the open slots is pointing away from the switch.  These
	slots are used to mount the switch to the cabinet.  Using the
	existing screws, mount the brackets to the switch.

  5. Install the switch with the correctly mounted brackets into the
     72-inch rack.
Comments: 
None   

---------------------------------------------------------------------------
Implementation Footnote: 
i)   In case of MANDATORY FINs, Enterprise Services will attempt to    
     contact all affected customers to recommend implementation of 
     the FIN. 
   
ii)  For CONTROLLED PROACTIVE FINs, Enterprise Services mission
critical    
     support teams will recommend implementation of the FIN  (to their  
     respective accounts), at the convenience of the customer. 

iii) For REACTIVE FINs, Enterprise Services will implement the FIN as
the   
     need arises.
----------------------------------------------------------------------------
All released FINs and FCOs can be accessed using your favorite network 
browser as follows:
 
SunWeb Access:
-------------- 
* Access the top level URL of http://sdpsweb.ebay/FIN_FCO/

* From there, select the appropriate link to query or browse the FIN and
  FCO Homepage collections.
 
SunSolve Online Access:
-----------------------
* Access the SunSolve Online URL at http://sunsolve.Corp/

* From there, select the appropriate link to browse the FIN or FCO
index.

Supporting Documents:
---------------------
* Supporting documents for FIN/FCOs can be found on Edist.  Edist can be 
  accessed internally at the following URL: http://edist.corp/.
  
* From there, follow the hyperlink path of "Enterprise Services
Documenta- 
  tion" and click on "FIN & FCO attachments", then choose the
appropriate   
  folder, FIN or FCO.  This will display supporting directories/files
for 
  FINs or FCOs.
   
Internet Access:
----------------
* Access the top level URL of https://infoserver.Sun.COM
--------------------------------------------------------------------------
General:
--------
* Send questions or comments to finfco-manager@Sun.COM
---------------------------------------------------------
Statusactive