230V AC Power Sequencer
| Servers: |
Enterprise E5x00, E6x00, 10000 |
Options 956 / 6513
| 300-1290 |
Sherwood Enterprises Model 10
Electronic Manufacturing Systems Model 10 |
| J3 Remote Power Control |
|
J4 Rack Fan Interface |
| PIN |
DESCRIPTION |
|
PIN |
DESCRIPTION |
| 1 |
Expansion Rack Fan Fail |
|
1 |
Rack Fan Fail |
| 2 |
Expansion Rack Fan Fail Return |
|
2 |
Ground |
| 3 |
+5V Power On Control |
|
3 |
Expansion Rack Fan Fail |
| 4 |
Remote In+ Keyswitch Closure+ |
|
4 |
Not Used |
| 5 |
Remote In- Keyswitch Closure- |
|
5 |
Not Used |
| 6 |
EPO+ Switch Closure+ |
|
6 |
Expansion Rack Fan Fail Return |
| 7 |
Not Used |
|
7 |
Not Used |
| 8 |
+5V Return |
|
8 |
Not Used |
| 9 |
EPO- Switch Closure- |
|
9 |
Expansion Rack Present In |
| J14 Remote In |
|
J15 Remote Out |
| PIN |
DESCRIPTION |
|
PIN |
DESCRIPTION |
| 1 |
Not Used |
|
1 |
Not Used |
|
| 2 |
Not Used |
|
2 |
Not Used |
| 3 |
Expansion Rack Fan Fail Out to Master |
|
3 |
Expansion Rack Fan Fail In from Slave |
| 4 |
Remote In+ Used as Slave |
|
4 |
Relay N.O. Remote Out |
| 5 |
Remote In- |
|
5 |
Relay Com. Remote Out |
| 6 |
Expansion Rack Fan Fail Return |
|
6 |
Expansion Rack Fan Fail Return |
| 7 |
Not Used |
|
7 |
Not Used |
| 8 |
Not Used |
|
8 |
Not Used |
| 9 |
Expansion Rack Present Out Connected to Pin-6 |
|
9 |
Expansion Rack Present In |
Operating Range
Nominal Voltage: 208, 220, 230, or 240 Volts AC
Operating Voltage: Single Phase 180-264 Volts AC
Frequency: 48-63Hz
Current: 24A maximum |
|