AC Power Sequencer
Remote and Local Bus Connectors

300-1263 300-1264 300-1126
300-1127 300-1155 300-1156

Remote I/O Connectors J6, J7, J8, and J9

A parallel circuit connects J6, J7, J8, and J9. Inputs to the Remote I/O Connectors are activated by mechanical toggle, key switch, transistor, integrated circuit, or thermoswitch with a normal open configuration.

CONNECTOR PART NUMBER USED WITH PART NUMBER
Female
Male
AMP 1-480304-0
AMP 1-480305-0
Socket Terminals
Contact Pins
AMP 60619-1
AMP 60620-1

Cable Description

Use 3-conductor, #22 AWG stranded wire.

Remote - OFF - Local Switch

POSITION DESCRIPTION
REMOTE AC output of the Switched 1 and Switched 2 outlets is enabled
when the breaker is ON and the Power Request is connected
to Signal Return on the Remote I/O Connectors.
OFF The AC output of the Switched 1 and Switched 2 outlets is disabled.
LOCAL The AC output of the Switched 1 and Switched 2 outlets is
enabled when the Circuit Breaker is ON.