Sun Microsystems, Inc.   Sun System Handbook - ISO 3.4 June 2011 Internal/Partner Edition
   Home | Current Systems | Former STK Products | EOL Systems | Components | General Info | Search | Feedback

24 Outlet AC Power Strip

Racks: Sun Rack 900, 1000

Option 6849

370-4946

Notes

  1. Each output group of four IEC320 Sheet F connectors is rated for 10A.
  2. The maximum combined output of all even output groups is 16A.
  3. The maximum combined output of all odd output groups is 16A.
  4. There is a 1.5 second delay between power on and power output.
  5. There is a 1.5 second delay between power on to each switched group.

  Copyright © 2011 Sun Microsystems, Inc.  All rights reserved.
 Feedback