Sun Type A239A
1030/2060 Watt Power Supply

Servers: Sun Fire X4470
Disk Arrays: Sun ZFS Storage 7420

Option X2362A

300-2228
Emerson AA25420L
AC Input Power Supply
Specification 950-5578
UL 60950-1 2nd Edition
EN 60950-1 2nd Edition
Power One SPASUNM-10G
AC Input Power Supply
Specification 950-5578
UL 60950-1 2nd Edition
EN 60950-1 2nd Edition


AC Input

100-127Vac 200-240Vac 50-60Hz 12A

DC Output

100-127Vac +12V 81.3A +3.3V 10A 1030W
200-240Vac +12V 165A +3.3V 10A 2060W

Efficiency

100V 10% Load >81%
>20% Load >85%
230V 10% Load >83%
20% Load >90%
50% Load >92%
100% Load >90%

Power Factor Correction

10% Load 20% Load 50% Load 100% Load
>0.80 >0.90 >0.95 >0.98

Notes

  1. Power Supply Efficiency affects the current draw in AC Watts from the branch circuit.
    As efficiency increases, the current draw in AC Watts decreases.
  2. To calculate maximum theoretical current draw in AC Watts,
    multiply the maximum power supply output in DC Watts by
    the reciprocal of the power supply efficiency.
  3. Theoretical values are typically higher than published values
    which are based on measured outputs under controlled test
    conditions.
  4. A two-CPU X4470 will run at 110V input.
    A four-CPU X4470 requires 220V input.
    See Sun Fire X4470 Installation Guide, 821-0332.