Sun Microsystems, Inc.   Sun System Handbook - ISO 3.4 June 2011 Internal/Partner Edition
   Home | Current Systems | Former STK Products | EOL Systems | Components | General Info | Search | Feedback

Sun SPARC® Enterprise M8000 Server: Hardware Specifications

Processor
Number Up to 16 CPUs
SPARC64 VI: Up to 32 Cores
SPARC64 VII: Up to 64 Cores
SPARC64 VII+: Up to 64 Cores
Architecture SPARC64 VI: 2.28GHz and 2.4GHz SPARC V9, ECC protected
SPARC64 VII: 2.52GHz SPARC V9, ECC protected
SPARC64 VII+: 3.00GHz SPARC V9, ECC protected
Cache memory SPARC64 VI: 6MB Shared Level 2 on Chip Cache per Processor, 128KB I-Cache and 128KB D-Cache Level 1 per Core
SPARC64 VII: 6MB Shared Level 2 on Chip Cache per Processor, 64KB I-Cache and 64KB D-Cache Level 1 per Core
SPARC64 VII+: 11MB Shared Level 2 on Chip Cache per Processor, 64KB I-Cache and 64KB D-Cache Level 1 per Core
System Boards
CPU/Memory Units (CMU) Up to 4
I/O Up to 4 External I/O Expansion Units
eXtended System Control Facility Unit (XSCFU) 2 (redundant)
Maximum Number of Domains 16
Main Memory
Maximum 1TB using 8GB DIMMs, 128 DIMM slots
Standard Interfaces
Ethernet 2 × 10/100 XSCF-LAN Ports per XSCFU
PCI Express 32 Slots, expandable up to 112 Slots, via optional external I/O Expansion Units
Serial 1 RJ-45 per XSCFU
USB 1 port per XSCFU that a field engineer can use to download hardware information
Internal Mass Storage
Disks Up to 16 disks, 4 per I/O Unit, 73GB, 146GB, or 300GB SAS Disk Drives supported
DVD-ROM 1
Tape 1 Optional DAT72 Tape Drive
Power Supplies
9 Power Supply Units (PSU) M8000 Base Cabinet
Environment
AC power 200 to 240 VAC
Power Consumption 10.5 kW (4 CMUs and 4 IOUs installed)
Apparent Power 11.0 kVA (4 CMUs and 4 IOUs installed)
Power Factor 0.9 or higher
Rush Current 100A0-p or less (current for each cable)
Leak Current 30mA or less
Heat output (cooling requirement) See Sun SPARC Enterprise M8000/M9000 Servers Site Planning Guide (819-4203)
There are a number of different power options available for the M8000. For more specific details on the specifications related to them, please see the Sun SPARC Enterprise M8000/M9000 Servers Site Planning Guide (819-4203).
Power cords See Sun SPARC Enterprise M8000/M9000 Servers Site Planning Guide (819-4203)
Temperature Operating:
Altitude 0 to less than 1500 Meters (0 - 4920 ft):
5° C to 32° C ( 41° F to 89.6° F)
Altitude 1500 to less than 2000 Meters (4921 - 6561 ft): 5° C to 30° C ( 41° F to 86° F)
Altitude 2000 to less than 2500 Meters (6562 - 8201 ft): 5° C to 28° C ( 41° F to 82.4° F)
Altitude 2500 to less than 3000 Meters (8202 - 9843 ft): 5° C to 26° C ( 41° F to 78.8° F)
Nonoperating: 0° C to 50° C ( 32° F to 122° F)
Humidity Operating: 20% to 80% relative humidity, noncondensing
Nonoperating: 8% to 80% relative humidity, noncondensing
Altitude Up to 3000M (9843 ft)
Regulations
Meets or exceeds the following requirements:
Safety CSA/UL-60950, EN60950, IEC950 CB Scheme with all national deviations
RFI/EMI EN55022/CISPR22 Class A, FCC CFR47 Part 15 Class A, EN61000-3-2, EN61000-3-3
Immunity EN55024, EN61000-4-2, -4-3. -4-5. -4-6, -4-8, and -4/11
Regulatory Markings CE, FCC, ICES, C-tick, VCCI, GOST-R, BSMI, MIC, CSA/UL
RoHS Compliance Level RoHS:YL
Other Marks WEEE and China RoHS
Dimensions and Weights
Height M8000: 180 cm (70.9 in.)
Power Expansion Cabinet: 180 cm (70.9 in.)
Width M8000: 75 cm (29.5 in.)
Power Expansion Cabinet: 31.7 cm (12.5 in.)
Depth M8000: 126 cm (49.6 in.)
Power Expansion Cabinet: 124.4 cm (49 in.)
Weight M8000: 700 kg (1540 lb.)
Power Expansion Cabinet: 350 kg (770 lb.)
Clearance and Service Access
Front 80cm (31.5 in)
Rear 80cm (31.5 in)
For more information, see the Sun SPARC Enterprise M8000/M9000 Servers Site Planning Guide (819-4203)

  Copyright © 2011 Sun Microsystems, Inc.  All rights reserved.