Sun Microsystems, Inc.   Sun System Handbook - ISO 3.4 June 2011 Internal/Partner Edition
   Home | Current Systems | Former STK Products | EOL Systems | Components | General Info | Search | Feedback

Sun Blade 6000 Modular System: Hardware Specifications

Note: These specifications are for the Sun Blade 6000 chassis.
Memory, CPU, storage, and I/O are Server Module (Blade) specific.
Reference the Servers/Blade section of the Sun System Handbook's Systems List to find Server Modules.

Capacity
Number
  • Up to 20 optional, hot-pluggable PCI ExpressModules (EM).
  • Up to 2 optional, hot-pluggable PCI Express Network Express Modules (NEM).
  • Up to 10 hot-pluggable Sun Blade Server Modules.
  • 2 (N+1), hot-plug / hot-swap 5600-Watt power supplies with independently wired fans.
  • 2 Front Fan Modules (6 fans total).
  • 6 Rear Fan Modules (12 fans total, N + 1 redundancy)
  • One Chassis Monitoring Module (CMM).
Management Environment
Sun Blade 6000 Chassis Monitoring Module (CMM)
  • Sun Blade 6000 chassis-level management is provided by the CMM's Integrated Lights-Out Management (ILOM) software.
  • Management can be integrated into Sun and/or third-party management tools.
  • Two ways to connect to CMM ILOM:
    • Connect a terminal or terminal emulation software to the SER MGT (RJ-45) port of the CMM to telnet into CMM ILOM.
    • Connect to the NET MGT 0 (10/100Base T ethernet) port of the CMM for Secure Shell (SSH) client access to CMM ILOM.
Power Supplies
Number Two, hot-plug / hot-swap, high-efficiency(~90%) power supplies are provided in a N+1 redundant configuration.
Output 5600-Watt per power supply.
Power Calculator Sun Blade 6000 - Power Calculator
Standard Integrated Interfaces
Network The Sun Blade 6000, without an optional EM or NEM, does not offer production network or I/O connectivity.
PCI Interfaces The Sun Blade 6000 Modular System I/O is architected using PCI Express technology. I/O is offered in two form factors: PCI Express ExpressModules (EM) and PCI Express Network Express Modules (NEM). Each server module has four PCI Express links.
Removable Media n/a
Environment
AC input
  • Voltage: 200-240 VAC.
  • Frequency: 50-60 Hz.
  • Current: 16A per AC input.
  • Number of AC Inputs: 4.
  • Maximum in-rush current: 32A.
  • Power Factor: 0.98.
  • AC Input Connection: Dependent on location:
    • AMER - L6-20P to IEC 320 C19; 2.5m; Sun PN 180-2005-01.
    • EPAC - IEC 309 to IEC 320 C19; 2.5m; Sun PN 180-2004-01.
    • Preinstalled in rack with power distribution unit - IEC 320 C20 to IEC 320 C19.
Airflow Requirements
  • Airflow (maximum) airflow inlet/outlet rate):1012 CFM (Cubic Feet per Minute).
  • Airflow (typical): 600 CFM (Cubic Feet per Minute).
  • Airflow direction: Front to rear.
Temperature Operating: 5°C to 35°C (41° F to 95° F) non-condensing.
Nonoperating: -40°C to 65°C (-40° F to 149° F) non-condensing.
Optimum ambient temperature: <23° C (73.40° F).
Relative Humidity Operating: 10% to 90% RH, non-condensing, 27° C max wet bulb.
Nonoperating: 5% to 93% RH, non-condensing, 38° C max wet bulb.
Optimum ambient relative humidity: 45% to 50% RH, non-condensing.
Altitude 0 to 10,000 feet (3,048m).
Sine Vibration Operating: Z (vertical)-axis: 0.15G X/Y axis: 0.10G 5 to 500 Hz sine.
Nonoperating: Z (vertical)-axis: 0.50G X/Y axis: 0.25G 5 to 500 Hz sine.
Shock 3Gs, 11msec, half sine (applied to rackmounted enclosure).
Regulations
Meets or exceeds the following requirements:
RoHS Compliance Level RoHS:YL
Product Safety
  • UL approved to UL 60950 and C22.2 No. 60950.
  • TUV approved to EN60950-1 and CB Report IEC 950 3rd Edition; including all amendments and full worldwide deviations.
  • GOST Certification.
  • Korean MIC Certification.
  • China CCC Mark for power supply only (system is exempt since it is rated greater than 1300W).
  • CE Declaration of Conformance to the Electronic Compatibility Directive and Low Voltage Directive with accompanying "Technical Data File".
  • Approval to Argentinian standards.
Laser Product and Optical I/O
  • FCC Regulation to Code of Federal regulations 21 CFR 1040-Lasers.
  • TUV approval to IEC 60825-1 Safety of Laser Products.
  • Canadian Radiation Emitting Devices Act REDR C1370.
Emissions and Immunities:
Electromagnetic Interference
  • 47 CFR 15B (Code of Federal Regulations, Part 15, Subpart B) Class A.
  • EN55022:1998 Class A per EMC directive 89/336/EEC (CE Mark).
  • VCCI Class A.
  • Industry Canada ICES-003.
  • AS/NZ 3548 (Australia/New Zealand).
  • CNS 13438 (Taiwan).
Immunity
  • EN55024:1998 per EMC Directive 89/336/EEC.
  • IEC 61000-4-2 Electrostatic discharge immunity test.
  • IEC 61000-4-3 Radiated, radio-frequency, electromagnetic field immunity test.
  • IEC 61000-4-4 Electrical fast transient/burst immunity test.
  • IEC 61000-4-5 Surge immunity test.
  • IEC 61000-4-6 Immunity to conducted disturbances, induced by radio-frequency fields.
  • IEC 61000-4-8 Power frequency magnetic field immunity test.
  • IEC 61000-4-11 Voltage dips, short interruptions, and voltage variations immunity tests.
Line Distortion EN 61000-3-2 per EMC Directive 89/336/EEC.
Voltage Fluctuations and Flicker EN 61000-3-3 per EMC Directive 89/336/EEC.
Dimensions and Weights
Chassis Height 438.15mm (17.25 in) - 10 RU minus clearance.
Chassis Width 444.5mm (17.50 in).
Chassis Depth 692.15mm (27.25 in).
Chassis Depth (in rack) 27.25 inches (692 mm) (distance from front vertical mounting rail to rear of the chassis).
Weight Fully configured system 160kg (350 lbs).
Empty Chassis:
35.7kg (78.7lbs).
Rack Mounting
Chassis=10R / 4 chassis max per 42U rack.

  Copyright © 2011 Sun Microsystems, Inc.  All rights reserved.