Solution Type Technical Instruction Sure Solution 1013594.1 : SL8500 - Calibration of Operator Panel Screen
PreviouslyPublishedAs 219143 Oracle Confidential (PARTNER). Do not distribute to customers Reason: Confidential for Partners and Oracle Support personnel
Applies to:Sun StorageTek SL8500 Modular Library SystemSun StorageTek SL8500 Modular Library System - Version: Not Applicable and later [Release: N/A and later] All Platforms Checked for relevance on 9-Feb-2011. GoalCalibration of Operator Panel Screen.SolutionSteps to FollowThe following information is found in "SL8500 Replaceable Parts Catalog, PN96139, Rev-E", page 343.
Calibration - Hardware Method If the operator panel requires calibration: 1. Power-off the operator panel. Note: If you do not close the DOS screen, the StreamLine Library Console application will activate within five seconds. Calibration - Firmware Method 1. At the screen, touch START -> Programs -> Penmount Utilities 2000 -> Penmount Control Panel 2. Select Calibrate 3. Perform steps 7 through 11 (above). Return to "Operator Panel." SL8500, Screen, How to Calibrate Op Panel Screen, Operator panel, Calibration, Control panel, Calibrate, Op Pane Previously Published As STKKB80297 Attachments This solution has no attachment |
||||||||||||
|