Sun System Handbook - ISO 3.4 June 2011 Internal/Partner Edition | |||
|
|
Solution Type Technical Instruction Sure Solution 1019462.1 : How to verify the power on the Sun Netra[TM] CT 900
PreviouslyPublishedAs 239905 Description This document describes how to verify the incoming power and power distribution within the Netra[TM] CT 900 Symptoms
Steps to Follow These are the steps to follow
The LEDs on each board will help to identify whether the problem is localized to a single board or affects a group of components or even the entire shelf. See <Document: 1019516.1>
The Netra CT900 has two redundant power entry modules known as PEMs located at the rear of the shelf. These PEMs take -48V DC power inputs and distribute power to the rest of the system. Each of the feeds should be individually protected via circuit breakers. The loss of an individual feed or a complete PEM should not cause the shelf to go down. If the shelf appears completely dead, i.e. no LEDS illuminated, or no sound of fans turning, verify external power is available and that the circuit breakers are in the on position. Any problems in this area may require the assistance of the site electrician.
Early model chassis referred to the Power Entry Modules as PEM-A and PEM-B. Later models refer to them as PEM-1 and PEM-2. The following table indicates the origin of each feed (numbered 0 through 7) and the zones they support (numbered 1 through 4).
If zone 2 and or zone 3 power is available, then one or both the shelf managers (ShMM) will power up and allow access to the system for further checks. Log into the active shelf manager using either the serial management port connection via the alarm card (refer to document <Document: 1019404.1> or through the network (assumes network connected and active). Refer to documents <Document: 1017986.1> and <Document: 1005533.1> verifying external network
# clia shmstatus Pigeon Point Shelf Manager Command Line Interpreter Host: "Active" #
Check the value for the parameter "Maximum External Available Current" for feed 00 through to feed 07 is showing 28 amps. If power is missing from an individual feed it will show 0 amps. This output also shows the FRU address for each of the boards on a particular feed. The "FRU Addr" given in this output is the Hardware Address of the board. To convert to a physical board refer to document <Document: 1019506.1> Example: # clia shelf power_distribution
Pigeon Point Shelf Manager Command Line Interpreter
PICMG Shelf Power Distribution Record (ID=0x11) Version = 0 Feed count: 8 Feed 00: Maximum External Available Current: 28.0 Amps Maximum Internal Current: 27.6 Amps Minimum Expected Operating Voltage: -40.5 Volts Actual Power Available: 1117.800 Watts Currently Used Power: 343.100 Watts Feed-to-FRU Mapping entries count: 3 FRU Addr: 45, FRU ID: 0xfe FRU Addr: 49, FRU ID: 0xfe FRU Addr: 4d, FRU ID: 0xfe Feed 01: Maximum External Available Current: 28.0 Amps Maximum Internal Current: 27.6 Amps Minimum Expected Operating Voltage: -40.5 Volts Actual Power Available: 1117.800 Watts Currently Used Power: 543.100 Watts Feed-to-FRU Mapping entries count: 6 FRU Addr: 41, FRU ID: 0xfe FRU Addr: 43, FRU ID: 0xfe FRU Addr: 47, FRU ID: 0xfe FRU Addr: 4b, FRU ID: 0xfe FRU Addr: 08, FRU ID: 0xfe FRU Addr: 10, FRU ID: 0x03 Feed 02: Maximum External Available Current: 28.0 Amps Maximum Internal Current: 27.6 Amps Minimum Expected Operating Voltage: -40.5 Volts Actual Power Available: 1117.800 Watts Currently Used Power: 330.000 Watts Feed-to-FRU Mapping entries count: 6 FRU Addr: 42, FRU ID: 0xfe FRU Addr: 44, FRU ID: 0xfe FRU Addr: 48, FRU ID: 0xfe FRU Addr: 4c, FRU ID: 0xfe FRU Addr: 09, FRU ID: 0xfe FRU Addr: 10, FRU ID: 0x04 Feed 03: Maximum External Available Current: 28.0 Amps Maximum Internal Current: 27.6 Amps Minimum Expected Operating Voltage: -40.5 Volts Actual Power Available: 1117.800 Watts Currently Used Power: 230.000 Watts Feed-to-FRU Mapping entries count: 4 FRU Addr: 46, FRU ID: 0xfe FRU Addr: 4a, FRU ID: 0xfe FRU Addr: 4e, FRU ID: 0xfe FRU Addr: 10, FRU ID: 0x05 Feed 04: Maximum External Available Current: 28.0 Amps Maximum Internal Current: 27.6 Amps Minimum Expected Operating Voltage: -40.5 Volts Actual Power Available: 1117.800 Watts Currently Used Power: 343.100 Watts Feed-to-FRU Mapping entries count: 3 FRU Addr: 45, FRU ID: 0xfe FRU Addr: 49, FRU ID: 0xfe FRU Addr: 4d, FRU ID: 0xfe Feed 05: Maximum External Available Current: 28.0 Amps Maximum Internal Current: 27.6 Amps Minimum Expected Operating Voltage: -40.5 Volts Actual Power Available: 1117.800 Watts Currently Used Power: 543.100 Watts Feed-to-FRU Mapping entries count: 6 FRU Addr: 41, FRU ID: 0xfe FRU Addr: 43, FRU ID: 0xfe FRU Addr: 47, FRU ID: 0xfe FRU Addr: 4b, FRU ID: 0xfe FRU Addr: 08, FRU ID: 0xfe FRU Addr: 10, FRU ID: 0x03 Feed 06: Maximum External Available Current: 28.0 Amps Maximum Internal Current: 27.6 Amps Minimum Expected Operating Voltage: -40.5 Volts Actual Power Available: 1117.800 Watts Currently Used Power: 330.000 Watts Feed-to-FRU Mapping entries count: 6 FRU Addr: 42, FRU ID: 0xfe FRU Addr: 44, FRU ID: 0xfe FRU Addr: 48, FRU ID: 0xfe FRU Addr: 4c, FRU ID: 0xfe FRU Addr: 09, FRU ID: 0xfe FRU Addr: 10, FRU ID: 0x04 Feed 07: Maximum External Available Current: 28.0 Amps Maximum Internal Current: 27.6 Amps Minimum Expected Operating Voltage: -40.5 Volts Actual Power Available: 1117.800 Watts Currently Used Power: 230.000 Watts Feed-to-FRU Mapping entries count: 4 FRU Addr: 46, FRU ID: 0xfe FRU Addr: 4a, FRU ID: 0xfe FRU Addr: 4e, FRU ID: 0xfe FRU Addr: 10, FRU ID: 0x05
#
The amount of power allowed by the Shelf manager for the slot is shown by the parameter "Maximum FRU Power Capabilities". Note: These values differ depending on the Chassis/ShMM firmware level. The amount of power requested by the board and subsequently allocated is shown by the parameter "Currently Assigned Power" If the board requests more power than is allowed for the slot, the board will not power up Example: # clia shelf -v power_management
Pigeon Point Shelf Manager Command Line Interpreter
PICMG Shelf Activation And Power Management Record (ID=0x12) Version = 1 Allowance for FRU Activation Readiness: 20 seconds FRU Activation and Power Description Count: 17 Hw Address: 41, FRU ID: 0xfe, Maximum FRU Power Capabilities: 235 Watts Shelf Manager Controlled Activation: Enabled Shelf Manager Controlled Deactivation: Enabled Delay Before Next Power On: 0.0 seconds Currently Assigned Power: 60.0 Watts
Hw Address: 42, FRU ID: 0xfe, Maximum FRU Power Capabilities: 235 Watts Shelf Manager Controlled Activation: Enabled Shelf Manager Controlled Deactivation: Enabled Delay Before Next Power On: 0.0 seconds Currently Assigned Power: 60.0 Watts
Hw Address: 43, FRU ID: 0xfe, Maximum FRU Power Capabilities: 235 Watts Shelf Manager Controlled Activation: Enabled Shelf Manager Controlled Deactivation: Enabled Delay Before Next Power On: 0.0 seconds Currently Assigned Power: 163.1 Watts
Hw Address: 44, FRU ID: 0xfe, Maximum FRU Power Capabilities: 235 Watts Shelf Manager Controlled Activation: Enabled Shelf Manager Controlled Deactivation: Enabled Delay Before Next Power On: 0.0 seconds Currently Assigned Power: 100.0 Watts
Hw Address: 45, FRU ID: 0xfe, Maximum FRU Power Capabilities: 235 Watts Shelf Manager Controlled Activation: Enabled Shelf Manager Controlled Deactivation: Enabled Delay Before Next Power On: 0.0 seconds Currently Assigned Power: 163.1 Watts
Hw Address: 46, FRU ID: 0xfe, Maximum FRU Power Capabilities: 235 Watts Shelf Manager Controlled Activation: Enabled Shelf Manager Controlled Deactivation: Enabled Delay Before Next Power On: 0.0 seconds Currently Assigned Power: 100.0 Watts
Hw Address: 47, FRU ID: 0xfe, Maximum FRU Power Capabilities: 235 Watts Shelf Manager Controlled Activation: Enabled Shelf Manager Controlled Deactivation: Enabled Delay Before Next Power On: 0.0 seconds Currently Assigned Power: 0.0 Watts
Hw Address: 48, FRU ID: 0xfe, Maximum FRU Power Capabilities: 235 Watts Shelf Manager Controlled Activation: Enabled Shelf Manager Controlled Deactivation: Enabled Delay Before Next Power On: 0.0 seconds Currently Assigned Power: 0.0 Watts
Hw Address: 49, FRU ID: 0xfe, Maximum FRU Power Capabilities: 235 Watts Shelf Manager Controlled Activation: Enabled Shelf Manager Controlled Deactivation: Enabled Delay Before Next Power On: 0.0 seconds Currently Assigned Power: 0.0 Watts
Hw Address: 4a, FRU ID: 0xfe, Maximum FRU Power Capabilities: 235 Watts Shelf Manager Controlled Activation: Enabled Shelf Manager Controlled Deactivation: Enabled Delay Before Next Power On: 0.0 seconds Currently Assigned Power: 0.0 Watts
Hw Address: 4b, FRU ID: 0xfe, Maximum FRU Power Capabilities: 235 Watts Shelf Manager Controlled Activation: Enabled Shelf Manager Controlled Deactivation: Enabled Delay Before Next Power On: 0.0 seconds Currently Assigned Power: 150.0 Watts
Hw Address: 4c, FRU ID: 0xfe, Maximum FRU Power Capabilities: 235 Watts Shelf Manager Controlled Activation: Enabled Shelf Manager Controlled Deactivation: Enabled Delay Before Next Power On: 0.0 seconds Currently Assigned Power: 0.0 Watts
Hw Address: 4d, FRU ID: 0xfe, Maximum FRU Power Capabilities: 235 Watts Shelf Manager Controlled Activation: Enabled Shelf Manager Controlled Deactivation: Enabled Delay Before Next Power On: 0.0 seconds Currently Assigned Power: 150.0 Watts
Hw Address: 4e, FRU ID: 0xfe, Maximum FRU Power Capabilities: 235 Watts Shelf Manager Controlled Activation: Enabled Shelf Manager Controlled Deactivation: Enabled Delay Before Next Power On: 0.0 seconds Currently Assigned Power: 0.0 Watts
Hw Address: 08, FRU ID: 0xfe, Maximum FRU Power Capabilities: 24 Watts Shelf Manager Controlled Activation: Enabled Shelf Manager Controlled Deactivation: Enabled Delay Before Next Power On: 0.0 seconds Currently Assigned Power: 20.0 Watts
Hw Address: 09, FRU ID: 0xfe, Maximum FRU Power Capabilities: 24 Watts Shelf Manager Controlled Activation: Enabled Shelf Manager Controlled Deactivation: Enabled Delay Before Next Power On: 0.0 seconds Currently Assigned Power: 20.0 Watts
Hw Address: 10, FRU ID: 0xfe, Maximum FRU Power Capabilities: 680 Watts Shelf Manager Controlled Activation: Enabled Shelf Manager Controlled Deactivation: Enabled Delay Before Next Power On: 0.0 seconds Currently Assigned Power: 327.0 Watts
Product Sun Netra CT 900 Server Netra CP3010 Board Netra CP3020 Board Netra CP3060 Board Sun Netra CP3220 ATCA Blade Server Sun Netra CP3250 ATCA Blade Server Sun Netra CP3260 ATCA Blade Server Sun Netra CP3140 ATCA Switch Blade Netra CP3240 Switch Internal Comments This document contains normalized content and is managed by the the Domain Lead (s) of the respective domains. To notify content owners of a knowledge gap contained in this document, and/or prior to updating this document, please contact the domain engineers that are managing this document via the "Document Feedback" alias(es) listed below: Domain Lead: Dencho.Kojucharov@sun.com Feedback Alias: blade_normalizers@sun.com normalized, verify, power, dead, ATCA, Netra, CT900, CP3010, CP3020, CP3060, CP3140, CP3240, CP3220, CP3250, CP3260 Attachments This solution has no attachment |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|