Solution Type Technical Instruction Sure Solution 1317384.1 : How to Remove and Replace X6440 FEM:ATR:2298:0
In this Document
Applies to:Sun Blade X6440 Server Module - Version: Not ApplicableInformation in this document applies to any platform. GoalX6440 FEM ReplacementSolutionDISPATCH INSTRUCTIONSWHAT SKILLS DOES THE ENGINEER NEED:(IS A SITE ENGINEER AVAILABLE?) X6440 trained DELIVERY REQUIREMENT: schedule with maintenance window Estimate AP Duration = 0.5 hours FIELD ENGINEER INSTRUCTIONS WHAT STATE SHOULD THE SYSTEM BE IN TO BE READY TO PERFORM THE RESOLUTION ACTIVITY? : * The server must be fully shut down and the power cords disconnected. * Do not operate the system with empty slots. Always insert a filler panel into an empty slot to reduce the possibility of system shut down. * Take ESD Precautions. WHAT ACTION DOES THE ENGINEER NEED TO TAKE: 1. Power off the server and remove the server module from the chassis 2. Remove the main cover 3. Remove the existing FEM board or the cap from the FEM connector if either is present. 4. Slide the FEM board at an angle into the support bracket, then press it carefully into the connector. Installation is the reverse of these procedures. OBTAIN CUSTOMER ACCEPTANCE WHAT ACTION DOES THE CUSTOMER NEED TO TAKE TO RETURN THE SYSTEM TO AN OPERATIONAL STATE: Verify functionality, no service LEDs or messages PARTS NOTE: REFERENCE INFORMATION: https://support.oracle.com/handbook_private/Systems/SunBladeX6440/component.top.html Maintenance and Operations Documentation http://download.oracle.com/docs/cd/E19045-01/blade.x6440/index.html Attachments This solution has no attachment |
||||||||||||
|