Solution Type Troubleshooting Sure Solution 1149403.1 : SL8500 - Instructions to Test Smoke Alarm
In this Document
Applies to:Sun Storage SL8500 Modular Library System - Version: Not ApplicableInformation in this document applies to any platform. PurposeInstructions to test the Smoke Alarm in the SL8500 library.Last Review DateJuly 14, 2010Instructions for the ReaderA Troubleshooting Guide is provided to assist
in debugging a specific issue. When possible, diagnostic tools are included in the document
to assist in troubleshooting.
Troubleshooting DetailsSmoke Detection:The air flow pattern is designed to draw air from the front of the library through the cartridge drive area, assuring that smoke in any part of the library will be accurately detected. In the event that a fire has produced excessive and dangerous smoke within the library, photoelectric smoke detectors (mounted in rear, upper right of the electronics and drive module) activate and all power shuts down. (Taken from SL8500 Install Manual) To test the Smoke Detector: Acquire a can of 'smoke' and spray over the detector. The library should EPO (power off) when the detector is functional. This is a Disruptive procedure and should be scheduled with the customer. Note: The 'TEST' letters on the smoke detector do not indicate any type of test button on the detector. Replacement of Smoke Detector: Removal and replacement of the smoke detector is now an annual preventive maintenance (PM) requirement. Remove and replace only the detector (non-disruptive), not the base (disruptive). Should there be a need for further fire detection information, refer to < Document: 1015903.1 > Attachments This solution has no attachment |
||||||||||||
|